S 2.20 Monitoring of existing connections

Initiation responsibility: Head of IT, Building Services Manager

Implementation responsibility: Building Services Manager, Planner

All distributors and duct boxes for the cabling must be visually inspected (spot checks at a minimum) at regular intervals. Attention must be paid to the following aspects:

A functional check can be performed in addition to the purely visual inspection. In this case, the necessity of existing connections is to be reviewed, and the connections must be checked for compliance with the technical parameters. For connections located in areas without access protection, it is recommended to perform this check in two cases:

All irregularities found during a visual inspection or functional check must be documented immediately, and the organisational unit responsible must be informed immediately so that the necessary measures can be initiated in a timely manner. It is also important not only to eliminate the irregularities found, but also to determine their cause.

Review questions: